Detailed Product Description
Application
range:
This circuit
breaker is applied to protect the over-current of electrical apparatus amd circuit decvice
of construction and similar buildings in the circuit of AC 50Hz,
rated voltage 230V and rated current 40A. It is also applied in the
unfrequent making-breaking
operation.
It accords with IEC60898:1995,
GB10963-1999 standard.
Main technical
parameter:
1. Frame size rated current Inm:
40A
2. Rated
voltage Ue: 50Hz, 230V.
3. Rated
current In: 6, 10, 16, 20, 25, 32, 40A.
4. Rated
breaking capacity Icn: 6000A.
5. Pole
number: 1P+N, width is 18mm.
6. Mechanical
life: 8000 times.
7. Electric
life: 4000 times.
8. The
tripping characteristic of circuit breaker is shown in Table 1 and
Drawing 1.


|