Detailed Product Description
Note: Standard reference conditions 27℃. (90°F)Air Inlet Temp.152.4m(500ft)A.S.L60% relative humidity. Generating Set under 50℃ Air Inlet Temp. is available
Standard Specifications
OUTPUT RATINGS (SC-DF SERIES GENERATOR)
The following 3 phase voltages are available:
50 Hz 415 400 380
240 230 220
60 Hz 460 440 416
266 254 240
Other voltages are available on request.
ENGINE
Sdec heavy duty industrial diesel engine.
Governor
Electronic governing standard on all 1000 series engines at 1500 / 1800 rpm.
Electrical System
24V system with battery charging alternator, axial type starter motor, high capacity maintenance free lead acid starting batteries, battery rack mounted on the generator set baseframe and heavy duty interconnecting cables with terminations.
Engine Filtration System
Sealed paper mesh type dry air filters. Cartridge type fuel filters and full flow lube oil filters. All filters have replaceable elements.
ALTERNATOR
Stamford / Marathon alternators have been carefully selected to match the overload performance of the engine and incorporate the following: Screen protected and drip proof, self exciting, self regulating brushless alternator with fully interconnected damper windings, IC06 cooling system and sealed for life bearings, PMG fitted as standard on BCP 1000 models and above. Other brand alternator are available on request.
Insulation System
The Insulation system is Class H.
All windings are impregnated in either triple dip thermo-setting moisture, oil and acid resisting polyester or vacuum impregnated with a special polyester resin. Heavy coat of anti-tracking varnish for additional protection against moisture or condensation.
Electrical Characteristics
Electrical design in accordance with BS5000-3, VDE0530, NEMA MGI-22/32, IEC34, CSAC22.2-100, and AS1359
|